Galaxy VS UPS 20kW 400V

In Stock
Add to Wishlist
Add to Wishlist

Add to Wishlist
Add to Wishlist
Compare
Category:

Description

Overview
Presentation Highly efficient, easy-to-deploy 20kW, 400V 3-phase UPS that brings best-in-class power protection and low total cost of ownership to edge, small and medium data centers, as well as to critical infrastructure in commercial and industrial applications. Includes 5×8 start-up service and 1 smart high-capacity modular battery string, expandable to 4 strings for extended runtime. Runtime charts available in the Documents tab.
Lead time Usually Ships within 2 Weeks
Main
Main Input Voltage 400 V 3 phases
Other Input Voltage 380 V
415 V
Main Output Voltage 400 V 3 phases
Other Output Voltage 380 V
415 V
Rated power in W 20 kW
Rated power in VA 20 kVA
Output connector type Hard wire 5-wire (3P + N + E) 1
Battery type Internal modular battery
VRLA
Provided equipment Battery modules ship installed
Dust filter
EcoStruxure IT ready (UPS)
Installation guide
Integrated network management
Power modules ship installed
Start-up service
General
Bypass voltage tolerance +/- 10 %
Redundant No
Physical
Colour White
Height 148.5 cm
Width 52.1 cm
Depth 84.7 cm
Net weight 320 kg
USB compatible No
Input
Network frequency 40…70 Hz
Number of input connectors 1 hard wire 4-wire (3P + E)
1 hard wire 5-wire (3P + N + E)
Input voltage limits 340…460 V 400 V
Maximum input current 36 A
Max short time withstand current 65 kA
Input harmonic distortion Less than 3 % for full load
Load power factor From 0.7 leading to 0.7 lagging without any derating
Input Power Factor at Full Load 0.99
Output
Maximum configurable power in W 20 kW
Harmonic distortion Less than 3 %
Output frequency 50 Hz sync to mains
60 Hz sync to mains
50 Hz +/- 0.1 % for 50 Hz nominal unsynchronised
60 Hz +/- 0.1 % for 60 Hz nominal unsynchronised
Crest factor 2.5
Wave type Sine wave
Output voltage tolerance +/-1% after 50ms
Output harmonic distortion < 1% linear load and < 3% non-linear load
Output overload operation 10 minutes at 125% and 60 seconds at 150%
Bypass type Built-in static bypass
Maximum configurable power in VA 20 kVA
Conformance
Product certifications UL 1778 5th edition
Standards CSA C22.2 No 107.3
EN/IEC 62040-1
EN/IEC 62040-2
EN/IEC 62040-3
IEC 60721-4-2 level 2M2
Environmental
Ambient air temperature for operation 0…40 °C
Relative humidity 0…95 % non-condensing
Operating altitude 0…3281 ft
Ambient air temperature for storage -15…40 °C
Storage Relative Humidity 0…95 % non-condensing
Storage altitude 0.00…3048.00 m
Acoustic level 55 dBA
Heat dissipation 2431 Btu/h
IP degree of protection IP20
Batteries & Runtime
Efficiency View Efficiency Graph

action_new_window
Battery voltage 480 V
Discharge battery voltage 384 V DC
Max current discharge 54 A
Battery power in VAH 0 VAh runtime
Extended runtime 0
Communications & Management
Free slots 1
Control panel Touch screen LCD user interface
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 168 cm
Package 1 Width 99 cm
Package 1 Length 64 cm
Package 1 Weight 360 kg

Reviews

There are no reviews yet.

Be the first to review “Galaxy VS UPS 20kW 400V”